AXL E EIP DI16 M12 6P 数据手册
https://www.phoenixcontact.com/pi/products/2701493
Distributed I/O device - AXL E EIP DI16 M12 6P - 2701493
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline E EtherNet/IP™ device in a plastic housing with 16 digital inputs, 24 V DC, M12 fast connection
technology
Why buy this product
■
■
■
■
■
■
Connection to EtherNet/IP™ network using M12connectors (D-coded)
Transmission speed of 10 Mbps and 100 Mbps
Connection of digital sensors using M12connectors (A-coded)
Diagnostic and status indicators
Short-circuit and overload protection of the sensor supply
IP65/IP67 degree of protection
Key Commercial Data
Packing unit
1 STK
GTIN
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
60 mm
Height
185 mm
Depth
30.5 mm
Note on dimensions
The height is 212 mm including fixing clips.
Drill hole spacing
198.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 %
Permissible humidity (storage/transport)
5 % ... 95 %
03/09/2016 Page 1 / 5
https://www.phoenixcontact.com/pi/products/2701493
Distributed I/O device - AXL E EIP DI16 M12 6P - 2701493
Technical data
Ambient conditions
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/IP67
General
Net weight
547 g
Mounting type
Wall mounting
Interfaces
Fieldbus system
EtherNet/IP™
Designation
EtherNet/IP™
Connection method
M12-Schnellanschlusstechnik
Note on connection method
D-coded
Designation connection point
Copper cable
Transmission speed
10/100 MBit/s (with auto negotiation)
Number of positions
4
System limits of the bus coupler
Designation
EtherNet/IP™
Equipment type
EtherNet/IP™ slave
System-specific protocols
EtherNet/IP™ protocols ACD
EtherNet/IP™ protocols DLR
EtherNet/IP™ protocols IGMP v2
Protocols supported
SNMP v1
HTTP
TFTP
FTP
BootP
DHCP
Specification
CIP Edition 3.11
EIP adaptation of CIP 1.12
Power supply for module electronics
Module electronics and sensors
M12 connector (T-coded) Module electronics and sensors (US) 4
Connection method
M12 connector (T-coded)
Designation
Module electronics and sensors (US)
Number of positions
4
Supply voltage
24 V DC
Nominal supply voltage range
18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption
max. 12 A
Typical current consumption
190 mA ±15 % (at 24 V DC)
Actuators
M12 connector (T-coded) Actuators (UA) for additional devices 4
Connection method
M12 connector (T-coded)
03/09/2016 Page 2 / 5
https://www.phoenixcontact.com/pi/products/2701493
Distributed I/O device - AXL E EIP DI16 M12 6P - 2701493
Technical data
Power supply for module electronics
Designation
Actuators (UA) for additional devices
Number of positions
4
Supply voltage
24 V DC
Nominal supply voltage range
18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption
max. 12 A
Typical current consumption
3 mA ±15 % (at 24 V DC)
Digital inputs
Input name
Digital inputs
Description of the input
EN 61131-2 types 1 and 3
Connection method
M12 connector, double occupancy
4-wire
Number of inputs
16
Protective circuit
Overload protection, short-circuit protection of sensor supply
Input filter time
< 1000 µs
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
11 V DC ... 30 V DC
Nominal input current at UIN
typ. 3 mA
Standards and Regulations
Conformity with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN 61000-4-3/IEC 61000-4-3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
Noise immunity test in accordance with EN 61000-6-2 Transient
overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply
lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4 Radio interference properties
EN 55022 Class A
Test section
24 V supply (communications power and sensor supply, digital inputs)/
bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, digital inputs)/
bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, digital inputs)/
FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet 1)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet 2)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet 1)/bus connection (Ethernet 2) 500 V AC 50
Hz 1 min.
24 V supply (actuator supply)/24 V supply (communications power and
sensor supply, digital inputs) 500 V AC 50 Hz 1 min.
03/09/2016 Page 3 / 5
https://www.phoenixcontact.com/pi/products/2701493
Distributed I/O device - AXL E EIP DI16 M12 6P - 2701493
Technical data
Standards and Regulations
24 V supply (actuator supply)/bus connection (Ethernet 1) 500 V AC 50
Hz 1 min.
24 V supply (actuator supply)/bus connection (Ethernet 2) 500 V AC 50
Hz 1 min.
24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min.
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period,
half-sine shock pulse
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Classifications
eCl@ss
eCl@ss 4.0
27240404
eCl@ss 4.1
27240404
eCl@ss 5.0
27242204
eCl@ss 5.1
27242604
eCl@ss 6.0
27242604
eCl@ss 7.0
27242604
eCl@ss 8.0
27242604
eCl@ss 9.0
27242604
ETIM
ETIM 2.0
EC001433
ETIM 3.0
EC001599
ETIM 4.0
EC001599
ETIM 5.0
EC001599
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
39121311
UNSPSC 12.01
39121311
UNSPSC 13.2
39121311
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
03/09/2016 Page 4 / 5
https://www.phoenixcontact.com/pi/products/2701493
Distributed I/O device - AXL E EIP DI16 M12 6P - 2701493
Approvals
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
cUL Listed
cULus Listed
Drawings
Connection diagram
Dimensional drawing
212
IN 6
+24 V
30,5
IN 5
185
IN 12
198,5
60
30
IN 11
+24 V
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
03/09/2016 Page 5 / 5